Formulas
Lateral pressure (ACI 347R-14, inch-pound units):
Walls, R < 7 ft/h and h ≤ 14 ft: p = Cw · Cc · (150 + 9000 R / T)
Walls, h > 14 ft or 7 ≤ R ≤ 15 ft/h: p = Cw · Cc · (150 + 43,400 / T + 2800 R / T)
Limits: 600 · Cw ≤ p ≤ w · h
Walls, R > 15 ft/h, or SCC: p = w · h
p in psf, R = rate of rise (ft/h), T = concrete temperature (°F), w = unit weight (lb/ft³), h = pour height (ft). 1 psf = 0.0479 kPa.
Material take-off (both faces):
Contact area = 2 × H × L Sheets = ⌈area × (1 + waste) ÷ sheet area⌉
Studs = (⌈L ÷ stud spacing⌉ + 1) × 2 Walers = ⌈H ÷ waler spacing⌉ rows × L × 2
Ties = ⌈L ÷ tie spacing H⌉ × ⌈H ÷ tie spacing V⌉
Tie load = p × tie spacing H × tie spacing V
Worked example
A wall 10 ft high and 40 ft long, placed at 5 ft/h at 70 °F, normal-weight concrete (150 lb/ft³), Type I cement without retarder:
- Cw = 1.0, Cc = 1.0; the wall is under 14 ft and R under 7 ft/h, so the first equation applies
- p = 150 + 9000 × 5 ÷ 70 = 793 psf (about 38 kPa)
- Check the limits: 600 ≤ 793 ≤ 150 × 10 = 1,500 psf ✓: 53% of full liquid head
- Ties at 24 × 24 in: 793 × 2 × 2 = 3.17 kips per tie
- Contact area = 2 × 10 × 40 = 800 ft² → 28 sheets of 4 × 8 ft with 10% waste
The same wall in metric (3 m high, 1.5 m/h, 20 °C) gives 38.4 kPa and 13.8 kN per tie at 600 × 600 mm.
How pour rate changes the pressure (3 m wall, 20 °C, normal concrete)
| Pour rate | Design pressure | Share of full liquid head |
|---|---|---|
| 0.5 m/h | 28.7 kPa (minimum governs) | 41% |
| 1.0 m/h | 28.7 kPa (minimum governs) | 41% |
| 1.5 m/h | 38.4 kPa | 54% |
| 2.0 m/h | 48.8 kPa | 69% |
| 3.0 m/h | 57.1 kPa (second equation, R > 2.1 m/h) | 81% |
| 5.0 m/h | 70.6 kPa (hydrostatic) | 100% |
Assumptions and limits
- Placement from the top with normal internal vibration no deeper than 1.2 m (4 ft) into the previous layer.
- Cw follows the concrete density: 1.0 between 2,240 and 2,400 kg/m³ (140–150 lb/ft³), lower for lightweight concrete (not below 0.8), higher for heavyweight.
- Studs are counted at both ends of each face. Walers and ties are counted one per spacing band, and double walers need twice the length.
- The calculator does not check plywood, stud or waler strength, deflection or bracing.