BUILDING & PLANNING · FIELD TOOL

Building Water Tank Planner

Storage = occupants × litres per person per day × days + fire reserve. 40 people at 135 L/day for one day plus 10,000 L fire reserve is 15,400 L. Split ⅓ / ⅔, that is a 5.1 m³ overhead tank (about 1.84 m square, 1.5 m deep) and a 10.3 m³ sump; filling the overhead tank in an hour needs about 85 L/min.

Free Account Required

Sign up free with your email or Google to use this calculator. It takes under a minute and unlocks every calculator on the site.

Behind this panel: an example with the default sizes.

Inputs

Results update as you type.

Demand
Tanks
m
m
Overhead tank and sumpStorage 15,400 Loverhead 5,082 Lsump 10,318 Lmyconstructioncalculator.comNot to scale
Diagram updates as you type.

Results

Check the working before you order.

Total storage
15,400L (15.4 m³)
Daily demand5,400 L (5.4 m³)
Overhead tank5,082 L (5.1 m³) ≈ 1.84 × 1.84 × 1.50 m water depth
Underground sump10,318 L (10.3 m³) ≈ 2.27 × 2.27 × 2.00 m water depth
Pump flow to fill the overhead tank85 L/min (1.41 L/s)
Price This optional: add your own prices

Your prices are remembered on this device only.

Send Order WhatsApp, SMS or email to your supplier
Include
Working
  1. Daily = 40 × 135 L = 5,400 L; total = daily × 1.0 + 10,000 fire = 15,400 L
  2. Overhead = 33% = 5,082 L; sump = 10,318 L
  3. Square tank side = √(volume ÷ water depth); add freeboard (typically 150–300 mm) to the internal height

Results are estimates for planning and material ordering only. They are not a substitute for structural design or approval by a qualified engineer. Read the full disclaimer.

Formulas

Daily demand = occupants × L per person per day
Storage      = daily × days + fire reserve
Overhead     = storage × overhead share;   sump = the rest
Square tank side = √(volume ÷ water depth)

Worked Example

40 occupants, 135 L/day, 1 day, 10,000 L fire reserve, ⅓ overhead at 1.5 m depth, sump at 2.0 m:

  1. Daily = 5,400 L; storage = 15,400 L
  2. Overhead = 5,082 L → ≈ 1.84 × 1.84 m; sump = 10,318 L → ≈ 2.27 × 2.27 m
  3. Pump to fill the overhead tank in 1 h ≈ 85 L/min

Tank Capacity by Size

Full capacity to the stated water depth. Usable volume is less once freeboard is left at the top.

Tank (L × W × depth) Cubic feet Litres US gallons
4 × 4 × 4 ft 64 ft³ 1,812 L 479 gal
5 × 5 × 5 ft 125 ft³ 3,540 L 935 gal
6 × 6 × 5 ft 180 ft³ 5,097 L 1,346 gal
8 × 6 × 5 ft 240 ft³ 6,796 L 1,795 gal
10 × 8 × 6 ft 480 ft³ 13,592 L 3,591 gal

How to Size a Building Water Tank

  1. Count the people the building serves.
  2. Pick the daily use per person from your local code (135 L in IS 1172 for homes).
  3. Multiply by the days of storage you want.
  4. Add any fire reserve the fire authority requires.
  5. Split the total between the overhead tank (often a third) and the underground sump.
  6. Choose a water depth and work out the tank sides, then add freeboard.

Frequently Asked Questions

How much water does a person use per day?

Planning figures vary, about 135–200 litres per person per day in homes and flats (IS 1172 suggests 135), around 45 litres per person in offices and day schools. Use your local code.

How big should an overhead water tank be?

Often about a third of the total storage, with the rest in an underground sump that a pump lifts from. Add fire reserve as the fire authority requires.

How much freeboard does a tank need?

Commonly 150–300 mm above the top water level, for the overflow and air gap.

How do I calculate water tank capacity in litres?

Multiply length × width × water depth. In metres, the answer × 1,000 is litres: 2 × 1.5 × 1.2 m = 3.6 m³ = 3,600 L. In feet, multiply the cubic feet by 28.32: a 5 × 5 × 5 ft tank holds 125 ft³, about 3,540 L.

How do I calculate the capacity of a round tank?

Volume = π × radius² × water depth. A tank 2 m across and 1.5 m deep holds 3.1416 × 1² × 1.5 = 4.71 m³, which is 4,712 L.