CONCRETE · CONCRETE COVER CALCULATOR

Concrete Cover for Beam

IS 456 sets a beam's nominal cover by exposure: 20 mm mild, 30 mm moderate and 45 mm severe, and never less than the bar diameter. Many specifications use 25 mm for beams inside buildings. ACI 318 asks for 1½ in (40 mm) to the stirrups in interior beams.

Inputs

Results update as you type.

Code, element & exposure
Concrete cover to reinforcement20 mmCover 20 mm to the outer barmyconstructioncalculator.comNot to scale
Diagram updates as you type.

Results

Check the working before you order.

Minimum cover
20mm
In inches0.79 in
Governing ruleIS 456:2000

Cover is to the outermost steel, including stirrups, ties and links. Fire rating or the drawings may require more.

Price This optional: add your own prices

Your prices are remembered on this device only.

Send Order WhatsApp, SMS or email to your supplier
Include
Working
  1. IS 456:2000 cl. 26.4, beam, 16 mm bars
  2. Table 16, mild exposure: 20 mm
  3. Table 16 note 2: the actual cover may be up to 10 mm more than the nominal cover, never less.

Results are estimates for planning and material ordering only. They are not a substitute for structural design or approval by a qualified engineer. Read the full disclaimer.

IS 456 Cover for Beams by Exposure

16 mm bars. Includes the rule that cover is never less than the bar diameter.

Exposure Nominal cover
Mild 20 mm
Moderate 30 mm
Severe 45 mm
Very severe 50 mm
Extreme 75 mm

ACI 318 Cover for Beams

Condition Specified cover
Not exposed to weather or ground 1½ in (40 mm)
Exposed to weather or ground, #5 and smaller 1½ in (40 mm)
Exposed to weather or ground, #6 and larger 2 in (50 mm)
Cast against and permanently in contact with earth 3 in (75 mm)

Worked Example

A beam with 16 mm bars in mild exposure, to IS 456:

  1. Table 16, mild exposure: 20 mm
  2. Not less than the bar diameter: 16 mm
  3. Nominal cover = 20 mm, measured to the outermost bar

More Concrete Cover by Element

Frequently Asked Questions

Why do many drawings show 25 mm cover for beams?

IS 456 allows 20 mm in mild exposure, but older practice (IS 456:1978) used 25 mm for beams and many engineers still specify it. The drawing always governs.

Is beam cover measured to the stirrup or the main bar?

To the outermost steel, which in a beam is the stirrup. The main bars sit one stirrup diameter further in.

What cover does a beam in a car park need?

Car parks see wetting, drying and de-icing or coastal salts, so IS 456 severe (45 mm) or more is common. Use the exposure your engineer specifies.

References

  • IS 456:2000 Table 16 and cl. 26.4 (nominal cover); Table 3 (exposure conditions)
  • ACI 318-19 Table 20.5.1.3.1 (specified concrete cover); NSCP 2015 uses the same values