CONCRETE · CONCRETE COVER CALCULATOR

Concrete Cover for Column

IS 456 asks for at least 40 mm of cover to column bars, or the bar diameter if larger, and more in severe exposure (45 mm) or very severe exposure (50 mm). Columns 200 mm or smaller with bars up to 12 mm may use 25 mm. ACI 318 and NSCP 2015 ask for 1½ in (40 mm) inside buildings.

Inputs

Results update as you type.

Code, element & exposure
Concrete cover to reinforcement40 mmCover 40 mm to the outer barmyconstructioncalculator.comNot to scale
Diagram updates as you type.

Results

Check the working before you order.

Minimum cover
40mm
In inches1.57 in
Governing ruleIS 456:2000

Cover is to the outermost steel, including stirrups, ties and links. Fire rating or the drawings may require more.

Price This optional: add your own prices

Your prices are remembered on this device only.

Send Order WhatsApp, SMS or email to your supplier
Include
Working
  1. IS 456:2000 cl. 26.4, column, 16 mm bars
  2. cl. 26.4.2.1: columns at least 40 mm
  3. cl. 26.4.2.1: columns 200 mm or smaller with bars up to 12 mm may use 25 mm.
  4. Table 16 note 2: the actual cover may be up to 10 mm more than the nominal cover, never less.

Results are estimates for planning and material ordering only. They are not a substitute for structural design or approval by a qualified engineer. Read the full disclaimer.

IS 456 Cover for Columns by Exposure

16 mm bars. Includes the 40 mm column minimum.

Exposure Nominal cover
Mild 40 mm
Moderate 40 mm
Severe 45 mm
Very severe 50 mm
Extreme 75 mm

ACI 318 Cover for Columns

Condition Specified cover
Not exposed to weather or ground 1½ in (40 mm)
Exposed to weather or ground, #5 and smaller 1½ in (40 mm)
Exposed to weather or ground, #6 and larger 2 in (50 mm)
Cast against and permanently in contact with earth 3 in (75 mm)

Worked Example

A column with 16 mm bars in mild exposure, to IS 456:

  1. Table 16, mild exposure: 20 mm
  2. Not less than the bar diameter: 16 mm
  3. Columns at least 40 mm (cl. 26.4.2.1)
  4. Nominal cover = 40 mm, measured to the outermost bar

More Concrete Cover by Element

Frequently Asked Questions

What is the cover for a column in NSCP 2015?

NSCP 2015 follows ACI 318-14: 1½ in (40 mm) for columns not exposed to weather, 2 in (50 mm) for #6 and larger bars exposed to weather, and 3 in (75 mm) cast against earth.

Is column cover measured to the ties?

Yes. Cover is to the outermost steel, which in a column is the ties or links. The vertical bars sit one tie diameter further in.

When can a column have 25 mm cover?

IS 456 cl. 26.4.2.1 allows 25 mm for columns of 200 mm or less in their smallest size whose bars do not exceed 12 mm.

References

  • IS 456:2000 Table 16 and cl. 26.4 (nominal cover); Table 3 (exposure conditions)
  • ACI 318-19 Table 20.5.1.3.1 (specified concrete cover); NSCP 2015 uses the same values